Designing for Liquid; What 45°C (113°F) Water Means for Your Next AI Data Center
Quick answer: AI data centers need liquid cooling because GPU racks now draw 120–230 kW, far beyond the roughly 40–50 kW air can handle. With 45°C (113°F) warm-water loops, heat moves from cold plates on each chip to dry coolers outdoors, often with no chiller and little or no water use.
Every AI data center we're asked to design today starts with the same question: how do we get the heat out? Air cooling has a ceiling, and GPU racks have gone straight through it. Liquid cooling is no longer an upgrade path. It is the starting point of a future-proof design.

Why can't air cooling handle AI racks?
Industry estimates put a Hopper-generation rack at about 40 kW, a Blackwell rack at 120–130 kW and a Vera Rubin NVL72 rack at 190–230 kW, with 2027's Kyber racks specified around 600 kW (Cyfuture). Air tops out around 40–50 kW per rack before fan power and hotspots get out of hand.
At CES in January 2026, NVIDIA CEO Jensen Huang said Vera Rubin draws about twice the power of Grace Blackwell, runs 100% liquid-cooled, and at a 45°C water supply doesn't need a chiller (Facilities Dive). Cooling isn't going away. It's changing shape.
What does 45°C (113°F) warm-water cooling change in the design?
Warm-water cooling flips a decades-old assumption. Instead of a chilled-water plant built around compressors, heat moves from the chip to a liquid loop and out to dry coolers. NVIDIA says its DSX reference design for AI factories uses zero water, and that a 50 MW facility could save more than $4 million a year in cooling energy and water (DataCenterNews).

Chillers don't vanish entirely. Memory, storage, networking and people still need conditioned air, and hot climates often keep a trim chiller (Network World). Most real facilities are hybrid: in one survey Network World cites, 42% of operators run air and liquid together and 12% are fully liquid-cooled. Rightsizing both systems is where good engineering pays off.
How does liquid cooling change construction and commissioning?
- CDUs become major plant. Coolant distribution units now ship in the megawatts, such as DCX's 8 MW unit built for 45°C Vera Rubin loops (Business Wire). Footprint, redundancy and service access belong in schematic design.
- Pipe is the new cable tray. Secondary fluid networks run to every rack, so routing, valving, leak detection and drip containment need the same rigor as electrical distribution.
- Floors carry more. Dense, liquid-filled racks concentrate several tonnes per position. Structural loading has to be verified, not assumed.
- Commissioning gets wetter. Flushing, filtration, fluid chemistry and pressure testing join the commissioning plan, and the operations team needs training before turnover.
Why choose the IT hardware and the cooling together?
Liquid cooling only works when the servers, racks and facility plant are designed as one system. That's why we bring hardware vendors into the design phase. Preferred server vendor MiTAC builds liquid cooling into the rack itself: at COMPUTEX 2026 it debuted a 52U high-density AI liquid-cooled rack (MiTAC Computing), and its OCP ORv3 43OU liquid-cooled rack holds up to 14 C2811Z5 multi-node servers (MiTAC Computing). Its flagship G4826Z5 is a 4U liquid-cooled server built around eight AMD Instinct MI355X GPUs (MiTAC). At the 2026 OCP Global Summit, MiTAC paired the G4826Z5 with ZutaCore's waterless two-phase cooling, which can support more than 4,000 W per chip with a modeled pPUE as low as 1.03 (MiTAC).
At the other end of the scale, Tonomia packages the whole loop. Its TonoForge AI factory, developed with engineering support from MiTAC, fits in about 50 m² with closed-loop liquid cooling, 300 kW with AMD MI355X or NVIDIA B300 and 500 kW with Vera Rubin, at a stated PUE of 1.05 (Tonomia founder, LinkedIn). Our affiliate Gray Wolf Data Centers builds liquid cooling and high-density power into every one of its AI/HPC facilities as standard.
Why does liquid cooling matter now?
Dell'Oro Group reported direct liquid cooling grew 85% in Q3 2025 and was on track to pass $2 billion in annual revenue (Fierce Network). Owners who build air-first today will be retrofitting tomorrow, and a retrofit costs far more than designing liquid in from day one.
Frequently asked questions
What rack density requires liquid cooling?
Air cooling generally tops out around 40–50 kW per rack. Current AI racks run 120–230 kW, so any facility built for Blackwell- or Vera Rubin-class GPUs needs liquid cooling.
Does a liquid-cooled AI data center still need chillers?
Often not for the GPUs. At a 45°C supply temperature, heat can be rejected through dry coolers. A small trim chiller may still serve air-cooled equipment, people spaces or hot climates.
What is a CDU in a data center?
A coolant distribution unit is a heat exchanger and pump skid that separates the rack-level coolant loop from the facility water loop. Units now reach the megawatt scale and should be planned early in design.
How INTUVA helps: we design, build, commission and manage liquid-cooled facilities, from the cold plate to the dry cooler. Explore our liquid cooling solutions or schedule a call to pressure-test your next AI project.
Disclosure: Pete Sacco is the Founder and CEO of PTS Data Center Solutions and Gray Wolf Data Centers. INTUVA and GRID7 are divisions of PTS. Gray Wolf Data Centers is a partnership between PTS, ReNew Developers, Tonomia and MiTAC.